1.
Introduction
1.1
Features of the Halon Fire Extinguishing System
1.1.1
Extinguishing Agent
Halon is an extinguishing
agent with excellent property, wide applications and high efficiency.
It can extinguish fire rapidly. The ejected extinguishing agent
is a clear and clean gas at atmospheric temperature and pressure
and will not leave any remains. The system is based on the chemical
extinguishing method.
Halon extinguishing
agent is a kind of compound which is composed by halogen atoms
replacing some or all hydrogen atoms of some low level alkyl compounds.
The commonly used halon extinguishing agents are 1211 and 1301.
The halon 1211 extinguishing
agent, or difluoro-chlo-bromamethane (the formula is CF2CIBr),
is a colourless, low poisonous and insulating gas with a bit of
smell. The halon 1301 extinguishing agent, or triflouro-brom-methane
(the formula is CF3Br), is a colourless and smell-less
gas with much lower poison than 1211.
1.1.2
The Structure of the System
(1) Metal-membrane
sealer of the container ensures an excellent air-tight seal and
makes permanent storage possible.
(2) Multi-start mode
(e.g., electric start, pneumatic start, electric-manual start
and jury mechanical-manual start) makes absolutely reliable start
assured.
(3) Special electric
start device decreases the start current to a lower level, which
has resulted in a great reduction in power for the control unit
and in volume of the battery and has made the system more compact.
(4) Particular design
of the bottle's straight-through valve reduces the flow resistance
of halon extinguishing agent to the minimum.
1.2
Application Scope
(1)
Halon extinguishing agent can be used to extinguish the A type
fire of combustible solids such as paper, wood, fabric, rubber,
etc. and the B type fire of all combustible liquids. It can also
be used for extinguishing C type fire of combustible gas.
(2)
Halon extinguishing agent can be used for extinguishing live electric
equipment fire and electric circuit fire.
(3)
Halon extinguishing agent can be used for the sites where valuable
articles or precious documents exist.
(4)
Halon extinguishing agent can be used for the sites where remains
cleaning is difficult after other extinguishing agent ejection.
(5)
Halon extinguishing agent can be used for the sites where no enough
space to store extinguishing agent while fire should be extinguished
by limited amount of extinguishing agent.
1.3
Exceptional Cases
(1)
Both the chemical matter that can burning rapidly without air
supply, such as cellulose nitrate, explosive, nitrogen oxide,
fluorine, etc. and the strong oxidants.
(2)
The active metal such as potassium, sodium, magnesium, titanium,
etc. and their oxidants.
(3)
Such chemical matter as peroxide and ammonia that can self-decompose.
(4)
Self-combustible matter, such as phosphorus.
2.
Technical Parameters of the System
2.1
Charging Pressure
Stationary
extinguisher:
1211
1.05 MPa; 2.5 MPa
1301 2.5 MPa; 4.2 MPa
Combined
distribution system:
1211
and 1301 2.5 MPa; 4.2 MPa
In general,
if the storage unit of extinguishing agent is far from the protection
area and the transport pipe is long, it is best to select high
storage pressure.
2.2
Charged Density of Extinghuishing Agent
(1)
1211: <= 1470 kg/m3
(2) 1301:
<= 1125 kg/m3
2.3
Ambient Temperature between Storage Bottles
(1)
1211: >= 7 oC
(2) 1301: usually >= -10 oC
2.4
Bottle Capacities
Capacity
of extinguishing agent bottles: 40 L; 70 L; 90 L
Capacity
of starting gas bottles: 3 L; 20 L
Starting
gas: N2
Working
pressure of starting bottle: 10 MPa
Maximum
single protection area: 500 m2
Maximum
single protection space: 200 m3
2.5
Start Mode
(1)
Electric start: DC 12 V ~ 28.8 V (60 W )
(2) Pneumatic start: gas pressure >= 0.35 MPa
(3) Jury mechanical-manual start: mechanical force < 50 N
2.6
Power Supply
Main
power supply: AC 220 V, 50 Hz
Reserve
power supply: DC 24 V
2.7
Ejecting Time of Extinghuisher and Start Delay
Start
delay: 0 ~ 30 s (adjustable)
Ejecting
time of extinguisher
(1) Gas and liquid protection areas: <= 10 s.
(2) Protection areas such as cultural relics room, archives office,
precious collections in library, etc.: <= 10 s.
(3) Other protection areas: <= 1 s.
2.8
Mounting Height of Collective Pipes and Select Valve
Mounting
height of collective pipes: <= 2400 mm;
Mounting
height of select valve: ~ 1500 mm.